Instructions for use of carbon dioxide fire extinguisher OU 3. Carbon dioxide fire extinguisher, portable. Instructions for use

A fire is a terrible incident that results in the loss of property, and sometimes life. Naturally, any source of ignition should be eliminated. An OU-3 fire extinguisher may be suitable for this.

The principle of operation of the device and its technical characteristics

This device works very simply. The fire extinguisher "OU-3" operates by displacing it from the cylinder, which is under pressure in it. After the shutter trigger mechanism works, carbon dioxide moves through the siphon tube to the socket. If it is in a liquefied state at rest, then at the moment of action it turns into a gas.

A feature of such a fire extinguisher is the instantaneous cooling of the combustion zone. In addition, the gas-air environment that blazes is quickly diluted with inert CO2. As a result, combustion stops.

Fire extinguisher "OU-3" has the following characteristics:

Jet length - 2.1 m.

The capacity of the flask is 4.3 liters.

The charge comes out in 8 seconds.

The weight of the device ready for use is 12.5 kg.

Use temperature - from - 40 to +50 degrees.

The term of operation, which is guaranteed by the manufacturer, is 1 year from the date of issue.

Scope of application

The OU-3 fire extinguisher is effective for where water-based fire extinguishers cannot be used.

It applies in the following cases:

1. In museums and galleries where valuable exhibits are stored that can be damaged by water.

2. For extinguishing electrical installations, the voltage in which does not exceed 1000 V.

3. To eliminate fire in trolleybuses, trams, trains.

4. For extinguishing gaseous, liquid and solid combustible substances.

This fire extinguisher can be used both indoors and outdoors.

Advantages, disadvantages and precautions

Note that such a device has certain advantages:

Leaves no traces after quenching.

The only drawback of the device in question is that it cannot be used to extinguish those substances that burn even without air. Here carbon dioxide will be simply useless.

As for the safety of use, the carbon dioxide fire extinguisher "OU-3" has some operational requirements:

1. If it is necessary to extinguish an electrical installation that is energized, then you should not approach it closer than one meter.

2. Do not recharge or repair the device yourself. For this, there are special service centers.

4. Do not point the bell at people during the release of CO 2, as the temperature of the gas is -60 degrees.

5. Do not leave the device in direct sunlight.

6. At least twice a year, check the operation of the device.

Instructions for use

The OU-3 fire extinguisher, the characteristics of which are discussed above, must be used strictly according to the instructions:

1. Bring the fire extinguisher close to the source of fire, observing the minimum allowed distance.

2. Point the bell in the direction where the fire is located, pull out the pin and press the handle that activates the device.

3. If the fire did not occur indoors, then try to direct the socket so that carbon dioxide does not come out against the wind.

4. After the extinguishing is completed, the device should be taken for refueling.

Keep in mind that a fire extinguisher can build up heat stress and try to extinguish the fire in such a way that carbon dioxide does not fall on you, as it has a toxic effect.

That's all the features of the application of the presented device. Good luck!

Fire extinguishers OU3 and OU5- portable CO² (carbon dioxide) fire extinguishers.

Fire extinguishers OU3 and OU5 are designed to extinguish the fire of various substances, the combustion of which cannot occur without access to air, fire on electrified railway transport, electrical installations under voltage not exceeding 10 kV, fire in museums, art galleries and archives, widespread use in office premises with office equipment, and also in the residential sector.

Carbon dioxide fire extinguishers are warehouse position and you can easily buy carbon dioxide fire extinguishers we have.

fire extinguishers CO2 ( carbon dioxide) OU-3 and OU-5 correspond to TU 4854-212-21352393-99 and are recognized as fit for operation. The release date of the fire extinguisher is marked on the locking head. The fire extinguisher complies with the fire safety requirements established in: GOST R 51057-01 and NPB 155-02.

The warranty period for storage and operation is 2 years from the date of manufacture, but not more than 1 year from the date of commissioning according to NPB 166-97.

Fire extinguishercarbon dioxide portable can be performed in two versions:

Option number 1: Fire extinguisher OU3;

Option #2: Fire extinguisher OU5.

Specifications:

  • Class B fire-extinguishing capacity: 10V-combustion of 10 liters of gasoline with a layer of 3 cm in a circle-shaped pan (13V-corresponding to 13 liters of gasoline, etc.).
  • The activation time of fire extinguishers is not more than 5 seconds.
  • Working pressure in the fire extinguisher body (calculated) at a temperature of 20`C 5.8 MPa.
  • The extinguishing agent is carbon dioxide (CO2) according to GOST 8050-85.

Meaning of indicators

Fire extinguisher body capacity, l

Mass of OTV (carbon dioxide), kg

Fire-extinguishing capacity (extinguishing a class B model fire)

Operating and storage temperature

From -20 o C to +50 o C

From -20 o C to +30 o C

Exhaust air jet length, m, not less than

Duration of putting the fire extinguisher into action, s, no more

Overall dimensions, mm, no more

Case diameter

Assigned service life of a fire extinguisher, years

Fire extinguisher full weight, kg, no more

Fire extinguisher consists of the following parts:

  • high pressure steel cylinder;
  • shut-off and starting device (LPU), threaded into the neck of the cylinder, equipped with a carrying handle and a lever for starting and interrupting the supply of fire extinguishing agent (OTV), as well as a check to prevent unauthorized operation of the fire extinguisher and a membrane that protects against excess pressure inside the cylinder over admissible;
  • a socket with a tube or hose for directing the OTV jet to the fire.

Job carbon dioxide fire extinguisher is based on the use of pressure created by saturated steam of carbon dioxide, which is also a fire extinguishing agent.

Carbon dioxide, getting into the combustion zone, lowers the concentration of oxygen in this zone, cools burning objects and knocks down the flame with a jet of OTV.

The intensity of the release of carbon dioxide depends on the ambient temperature, at a positive temperature it increases, at a negative temperature it decreases.

Contents of delivery:

Package Included:

  • Carbon dioxide fire extinguisher;
  • Bell with hose (for OU-5);
  • Bell with a discharge pipe (for OU-3);
  • Operation manual - 1 copy.

Life time:

Service life 10 years.

Requirements for safety and environmental protection.

1. Do not allow moisture to enter the fire extinguisher.

2. Fire extinguishers must be installed in such a way that their top is located at a height of no more than 1.5 m from the floor. They can be installed on the floor, with mandatory fixation from a possible fall in case of accidental impact.

3.Disposal fire extinguisher carried out by specialized companies.

Operating instructions

1. Contents of input control:

1.1 The need for input control and the number of products subject to input control is determined by the customer (consumer).

1.2. Carry out an external inspection carbon dioxide fire extinguisher.

  • the presence of dents, chips, deep scratches on the body, control units, nuts and fire extinguisher head;
  • condition of protective and paint coatings;
  • the presence of clear and understandable instructions;
  • the presence of a sealed safety device;
  • the presence of the necessary stamp;
  • mass fire extinguisher, as well as the mass of the fire extinguishing agent in the fire extinguisher (the latter is determined by calculation);
  • the condition of the flexible hose (if any) and the OTV sprayer (presence of mechanical damage, traces of corrosion, casting flash or other objects preventing the free exit of the OTV from the fire extinguisher);
  • reliability of mounting the fire extinguisher body on the wall or in the fire cabinet.

Based on the results of the check, the necessary marks are made in the fire extinguisher's passport, it is assigned a serial number, which is applied to the fire extinguisher and recorded in the fire extinguisher register.

2. Certification

2.1 Survey fire extinguisher should only be carried out at service stations.

2.2. A quarterly check includes an inspection of the installation site of the fire extinguisher and approaches to it, as well as an external inspection of the fire extinguisher.

2.3. Weigh the fire extinguisher at least once a year. Permissible leakage of OTV is no more than 50 g per year.

2.4. At least once every 5 years, the body of the fire extinguisher must be re-examined in accordance with the requirements of the "Rules for the Design and Safe Operation of Pressure Vessels"

3. Repair. Forbidden carry out any repair work and disassembly of the fire extinguisher in the presence of pressure in the fire extinguisher body;

4. Use of the product for its intended purpose.

4.1. Use of the product for purposes other than those intended FORBIDDEN

4.2. Charging, recharging and maintenance of fire extinguishers should be carried out only at fire extinguisher service stations.

4.3. Persons operating fire extinguishers must be familiar with the rules of use in accordance with the instructions.

4.4. Casting method fire extinguisher operation and options for its use are indicated on the label placed on the fire extinguisher body.

4.5. When extinguishing a fire, it is necessary to bring the fire extinguisher to the source of combustion (approach from the windward side, no closer than 1 m), break the seal, pull out the pin, point the socket at the source of combustion, aiming at the base of the flame, press the lever of the shut-off device and start extinguishing the source fire, approaching it as it is extinguished, but not stepping inside the hearth.

4.6. When extinguishing electrical equipment under voltage, it is not allowed to bring the socket or body fire extinguisher to open current-carrying parts with voltage up to 1000 V closer than 1 m.

4.7. Exploitation fire extinguisher without checks and seals of the manufacturer (or reloading) is not allowed.

4.8. Care must be taken when releasing carbon dioxide from the socket, as the temperature of its surface and hose drops to -60...-70°C.

4.9. Care must be taken when applying fire extinguishers, since there is a danger of toxic effects of carbon dioxide vapor on the human body.

4. 10. After application fire extinguisher in a closed room, it is necessary to immediately ventilate the room, as the oxygen content in the room air decreases.

4.11. After application fire extinguisher should be immediately sent for recharging, replacing it with the same type of backup fire extinguisher.

5.Transportation and storage.

5.1. Conditions of transportation and storage mobile fire extinguishers must comply with the requirements of GOST 15150.

5.2. Transportation of mobile vehicles is allowed fire extinguishers by all modes of transport for any distance in accordance with the rules for the carriage of goods in force for a particular mode of transport.

5.3. Transportation fire extinguishers aircraft is allowed only in pressurized compartments.

5.4. During transportation and storage fire extinguishers conditions must be provided to protect them from mechanical damage, heating, direct sunlight, precipitation, exposure to moisture and aggressive environments.


The carbon dioxide fire extinguisher OU-3 is designed to extinguish initial fires of class B and C. This class includes fires of household electrical appliances (TVs, computers, refrigerators, etc.) :

Petrol,
- kerosene,
- machine oils,
- diesel fuel

The fire extinguishing capacity of the OU-3 is at least 34V, which means that during its operation, the carbon dioxide extinguishing mixture is able to completely extinguish at least 34 liters of burning gasoline, spilled in a layer of 3 centimeters, located in a baking sheet having the shape of a circle (laboratory conditions). In real conditions, this fire extinguisher is enough to eliminate class B and C fires.

Pressure

The working pressure of the charged UO-3 should not be less than 5.88 mPa. This pressure provides a uniform and dense release of the fire extinguishing mixture for 8 seconds, at a distance of at least 3 meters.

Best before date

The service life of a carbon dioxide fire extinguisher OU-3 is at least 5 years. After servicing the valve mechanism and recharging, the fire extinguisher receives all its original properties.

Weight

With a capacity of the body of the OU-3 carbon dioxide fire extinguisher of 3 liters, its weight in the filled state should be at least 9.3 kg. In this case, the mass of the fire extinguishing agent must be at least 2.85 kilograms.

Precautionary measures

When the mixture is ejected from the nozzle, its volume, coming into contact with the environment, increases by 400-500 times while reducing the temperature of the mixture to minus 72 degrees Celsius. The elimination of fires is achieved by lowering the temperature of the hearth below the combustion temperature and by displacing oxygen through the flow of chemical processes when the mixture and combustion products come into contact. When working with this apparatus, precautions should be taken to prevent contact of the mixture with the eyes and digestive organs. Analog OU-3 - fire extinguisher VVK-2.

Video review of OU-3

  1. "CO2 fire extinguisher OU-3 (h) (B, C, E)"- works on the principle of exclusion of oxygen in the combustion chamber.
  2. Due to the fact that after use the carbon dioxide fire extinguisher "OU-3" does not leave marks, it is widely used at facilities where there is a risk of short circuit, for example, at substations, industrial enterprises, industrial warehouses.
  3. Carbon dioxide fire extinguishers do an excellent job of igniting combustible gases, paints, oils, fuels, so gas stations are equipped with them.
  4. Using the OU-3 carbon dioxide fire extinguisher, you do not need to worry about dust or clogging of the room, after drying there are no traces left.
  5. "CO2 fire extinguisher OU-3 (h) (B, C, E)" are ideal for libraries, hospitals, schools. The storage range of a carbon dioxide fire extinguisher is from -40C to +50C, which is perfect for our latitudes, and the service life of the fire extinguisher is 10 years.

Instruction

  1. "Carbon dioxide fire extinguisher OU-3 (h) (B, C, E)" copes with fire due to the displacement of the carbon dioxide charge, under the influence of its own excess pressure, which is created in the fire extinguisher.
  2. Carbon dioxide is in a cylinder under a pressure of 5.7 MPa (58 kgf/cm2) at an ambient temperature of 20°C.
  3. The maximum working pressure in the fire extinguisher cylinder at a temperature of +50°C should not exceed 15 MPa (150 kgf/cm2).
  4. When opening the shut-off-starting device (LPU), the charge of carbon dioxide through the siphon tube enters the socket. When this occurs, the transition of carbon dioxide from a liquefied state to a solid (snow-like) state, accompanied by a sharp drop in temperature to minus 70°C.
  5. The fire-extinguishing effect of carbon dioxide is based on cooling the combustion zone and diluting the combustible vapor-gas-air medium with an inert (non-combustible) substance to concentrations at which the combustion reaction stops.
  6. To bring the "OU-3" into action, it is necessary to pull out the pin.
  7. Direct the fire extinguisher bell at the fire from a distance of 3 meters from the windward side.
  8. With a hand, press the handle of the locking device (LPU), carbon dioxide is released under high pressure (fire extinguishing agent (OTV)).
  9. While using the "OU-3", it is necessary to hold the fire extinguisher socket by the plastic part, otherwise there is a risk of frostbite.

Specifications

Application area

"CO2 fire extinguisher OU-3 (h) (B, C, E)" is used to extinguish combustible substances of the class:
  1. B
    • combustion of liquid substances insoluble in water (for example, gasoline, ether, petroleum products). Also, combustion of liquefiable solids (eg paraffin, stearin);
    • combustion of liquid substances soluble in water (for example, alcohol, glycerin).
  2. C
    • combustion of gaseous substances, household gas, propane and others.
  3. E
    • burning electrical installations, electrical wiring under voltage.

How to buy "CO2 fire extinguisher OU-3" and can the price be lower?

The price is 1139.00 rub. The site is presented for retail. However, the company "PozhZashchita.RU" individually works with wholesale buyers, providing the best and competitive cost of commodity items. This is made possible through direct cooperation with manufacturers of products without intermediaries.

Regarding the purchase of this product:

  • You can buy "CO2 fire extinguisher OU-3" right on this page, indicating all the additional options;
  • use the simplest way, the quick order form;
  • contact directly with our manager, who will give you all the comprehensive information on the product, as well as provide professional advice on issues of interest.

How to receive the ordered goods or delivery methods

Our firm has representative offices in Krasnodar, Rostov-on-Don, St. Petersburg, Sevastopol and Simferopol. This means that you can buy or receive your purchase from a pickup point. For other regions of Russia, we offer delivery with various types of carrying capacity and volume of the car body, urgent delivery or door-to-door delivery, cargo insurance and much more. We provide all the details on the cost and other questions on transportation when registering the shipment together with the carrier, since the number of ordered products may vary significantly.

Availability and consultation

A product such as "CO2 fire extinguisher OU-3" available almost always. When ordering in bulk, the required quantity will be delivered directly from the manufacturer's warehouses, providing the client with everything necessary. Don't forget that the best price on the market can be offered for you. If you are in doubt about the choice, be sure to look at related positions from section "Carbon dioxide" on the site. Also, do not hesitate to get all the detailed information about the "CO2 Fire Extinguisher OU-3" from our specialists.

Complies with GOST R 51057-2001 " Fire fighting equipment. Fire extinguishers are portable. General technical requirements. Test Methods"

Description:

One of the most widely used fire extinguishers. Great as a car fire extinguisher, for those who want protection more reliable than the minimum allowable OU-2. Such a fire extinguisher is usually installed in switchboard and server rooms.

Carbon dioxide fire extinguishers not designed to extinguish solid combustible substances !!! Materials such as wood, paper, textiles, etc. after using a carbon dioxide fire extinguisher, they will continue to smolder and may catch fire again!

It is preferable to equip with carbon dioxide fire extinguishers electrical panel, server, fire panels in paint shops, gas stations and on the territory of industrial enterprises, as well as in museums, art galleries and archives, due to the fact that a carbon dioxide fire extinguisher does not leave behind a powder (as is the case with a powder fire extinguisher) .

Designed for use:

  • on passenger vehicles - 1 pc, on freight, passenger vehicles - 2 pcs,
  • to extinguish fires in rooms of categories B, public premises, fires of class E (electrical equipment) up to 10,000 V, at the rate of 1 fire extinguisher per 100 m 2 ;
  • for extinguishing electrical installations with voltage up to 10,000 V;
  • to extinguish computer technology;
  • extinguishing liquid and gaseous combustible substances of small volumes

Specifications:

  • body capacity - 4.02 l;
  • the mass of the CO 2 charge is 3 kg;
  • fire extinguishing capacity - 34V
  • temperature mode of operation - from -40 to +50 °С;
  • OTV jet length - 3 m;
  • working pressure - 5.8 MPa;
  • the duration of the supply of OTV - 8 seconds;
  • fire extinguisher weight (gross) - no more than 10.5 kg;
  • service life - 10 years.

Maintenance:

During the operation of the fire extinguisher, it is necessary to carry out its timely maintenance at specialized stations, in the amount of:

  • re-examination (checking parameters) - annually;
  • recharge - 1 time in five years, after use, when pressure drops;
  • fire extinguishers installed on vehicles must be recharged at least once every 24 months;
  • fire extinguishers mounted on vehicles outside the cab or interior and exposed to adverse climatic and physical factors, must be recharged at least once every 12 months.

Accommodation:

On vehicles, fire extinguishers must be located in the cab, in close proximity to the driver or in a place easily accessible to him. Do not store fire extinguishers inplaces, access to which is difficult (trunk, body, etc.).

In buildings, a fire extinguisher is located near the places of the most likely occurrence of a fire, along evacuation routes, and also near the exit from the premises. in such a way that it is protected from direct sunlight, heat fluxes, mechanical influences and other adverse factors. Need to ensuregood visibility and easy access in case of fire.

Typically, a fire extinguisher is hung on a bracket, while the top of the fire extinguisher should be located at a height of no more than 1.5 m from the floor. It is also possible to installin a fire cabinet or on a special stand.

Usage:

To use a fire extinguisher, you need to follow these simple steps:

  1. Pull out the pin by the ring, which prevents the fire extinguisher from accidentally working, while the safety seal is broken;
  2. Direct the bell to the place of fire and press the lever.
  3. Attention! When carbon dioxide escapes, a sharp cooling of the fire extinguisher bell occurs.

Extinguishing methods:

Passport:

Similar posts